DSpace Repository

THEORETICAL INVESTIGATION OF VAPOR COMPRESSION COOLING CYCLE USING HFO-1234yf and HFO-1234ze

Show simple item record

dc.creator Ozgur, Arif Emre
dc.date 2013-08-31T21:00:00Z
dc.date.accessioned 2020-10-06T09:47:34Z
dc.date.available 2020-10-06T09:47:34Z
dc.identifier 39a1eda3-5359-4c63-a70a-4aa96e903d50
dc.identifier https://avesis.sdu.edu.tr/publication/details/39a1eda3-5359-4c63-a70a-4aa96e903d50/oai
dc.identifier.uri http://acikerisim.sdu.edu.tr/xmlui/handle/123456789/57639
dc.description In this study, effects of using HFO-1234yf and HFO-1234ze recommended as an alternative refrigerant on cycle performance and exergetic efficiency are presented. Because of HFO-1234yf and HFO-1234ze are suggested as alternatives of HFC-134a, the cycle performance and cycle exergetic efficiency parameters are presented comparatively for the refrigerants at the same working conditions and the same cycle. The effects of refrigerant changing process are discussed. It was concluded that from the results, the cycle performance and exergetic efficiency are almost same for HFC-134a and HFO-1234ze and higher than to HFO-1234yf. The difference between these values is 15% for 50 degrees C condensing temperature.
dc.language tur
dc.rights info:eu-repo/semantics/closedAccess
dc.title THEORETICAL INVESTIGATION OF VAPOR COMPRESSION COOLING CYCLE USING HFO-1234yf and HFO-1234ze